Documents

Water Service Installation Detail

View original document →

Overview

This document is a technical schematic for the installation of a residential water service line, issued by the Borough of Ebensburg. It outlines the specific piping layout, component requirements, and installation standards for connecting a property to the municipal water supply.

Installation Specifications

The diagram details the sequence of components required from the street to the interior of the building:

  • Source: The line originates "From Curb Stop. "
  • Entry Point: A copper inlet pipe enters through the interior basement wall.
  • Valves and Controls:
    • A shut-off valve is required immediately after the inlet.
    • A pressure reducer must be installed to regulate water pressure.
  • Metering:
    • A water meter is required with a minimum size of 5/8 inches.
    • The meter must be obtained from the Borough.
    • A wire connection to a remote readout is required.
  • Safety: A backflow preventer must be installed on the line leading to the customer.

Technical Requirements

  • Piping Height: The center of the piping must be installed 2' to 4' above the basement floor and 6" from the wall.
  • Pipe Size: The minimum pipe size is 3/4", though it should match the existing pipe size.
  • Clearance: There must be a minimum of 6" clearance between the pipe and the basement floor.
  • Adaptors: A specific "Pipe to Meter Adaptor" is required for the connection.

Administrative Details

  • Issuing Authority: Borough of Ebensburg, Pennsylvania.
  • Engineering Firm: L. Robert Kimball & Associates, Inc. , based in Ebensburg.
  • Revision Date: The document was updated in May 2024.