Overview

This document is a technical engineering diagram titled "Service Connection to Sanitary Sewer with Trap and Vent. " It provides specifications for connecting a building's plumbing system to the municipal sanitary sewer, specifically detailing requirements for backflow prevention and venting.

Key Components and Specifications

The diagram outlines the following hardware and installation standards:

  • Frame and Cover: Must be East Jordan Iron Works Inc. (Pattern No. 1565) or Neenah Model No. R-1975-A2 (or equal).
  • Piping Material: The trap, vent, and cleanout assembly must be PVC, Schedule 40 pipe and fittings.
  • Connection to Lateral: Use a coupling of the same type as the pipe (SDR-35) or adapt to Sch. 40 if applicable.
  • Cleanout: A cleanout pipe is required with a length as needed (req'd).
  • Backflow Prevention: A backflow prevention device is marked as optional but recommended.
  • Venting: An air vent cap is required, extending at least 12 inches above the ground.

Installation Dimensions and Clearances

  • Minimum Depth: The assembly must be buried at a minimum depth of 2 feet, 8 inches.
  • Clearance: There must be a minimum of 24 inches between the vertical stack and the building wall.
  • Building Wall Proximity: The sanitary tee connection to the building sewer must be no more than 5 feet, 0 inches from the building wall.
  • Concrete Encasement: The view port stack requires Class "A" concrete and full-depth AASHTO #57 aggregate with a 1/2-inch minimum void all around.

Notes

  • A 4-inch view port stack is acceptable in cases where the service stub is 4 inches.
  • The diagram includes a "Property or Easement Line" indicator to ensure proper placement relative to property boundaries.